YANG Yan-qiu, YANG Liang, YANG Tong-zai, HAO Fan-hua, LUO Shun-zhong, YE Shi-you, JIANG Tao, HE Yu-hui, WANG Li-xiong, TIAN Jie, YANG Jun. Air Leakage Test of Reactor Hall Using Tracer Technique[J]. Atomic Energy Science and Technology, 2011, 45(5): 582-587. DOI: 10.7538/yzk.2011.45.05.0582
Citation: YANG Yan-qiu, YANG Liang, YANG Tong-zai, HAO Fan-hua, LUO Shun-zhong, YE Shi-you, JIANG Tao, HE Yu-hui, WANG Li-xiong, TIAN Jie, YANG Jun. Air Leakage Test of Reactor Hall Using Tracer Technique[J]. Atomic Energy Science and Technology, 2011, 45(5): 582-587. DOI: 10.7538/yzk.2011.45.05.0582

Air Leakage Test of Reactor Hall Using Tracer Technique

More Information
  • Received Date: December 31, 1899
  • Revised Date: December 31, 1899
  • The leakage ratios of three related reactor halls were tested by sulfur hexafluoride gaseous tracer technique. Moreover, the accumulation intensities of leak gas and its retention time in some important working rooms, the crossroads of corridors and anteroom of the building were detected. The results show that the air leakage ratios of the three reactor halls are (7.30±0.16)×10-4,(1.88±0.12)×10-4 and (2.07±0.07)×10-4h-1. The leak gas accumulates in all the detected working rooms fast, and the retention time to various rooms is about 5 h. The heaviest intensities are in the clothes change rooms on the first floor. However, the retention time to the crossroads and the anteroom is about 10 h, and the accumulation intensities are much small.
  • [1]
    羊衍秋,杨通在,邢丕峰. 全氟碳化合物示踪技术及应用[J]. 气候与环境研究,2003,8(4):485-494.
    YANG Yanqiu, YANG Tongzai, XING Pifeng. Perfluorocarbon tracer technology and application[J]. Climatic and Environmental Research, 2003, 8(4): 485-494(in Chinese).
    [2]
    RUSSELL N D, EDGAR A C, GUNNAR I S, et al.An inexpensive perfluorocarbon tracer technique for wide-scale infiltration measurements in homes, BNL-30032[R]. US: Brookhaven National Laboratory, 1981.
    [3]
    RUSSELL N D, EDGAR A C. Air infiltration measurements in a home using a convenient perfluorocarbon tracer techniqiue[J]. Environment International, 1982(8): 419-433.
    [4]
    SHERMAN M H. Air infiltration measurement techniques, LBL-27656[R]. Berkeley, California: Lawrence Berkeley Laboratory, University of California, 1998.
    [5]
    SHERMAN M H. Uncertainty in air flow calculations using tracer gas measurements, LBL-25415[R]. Berkeley, California: Lawrence Berkeley Laboratory, University of California, 1998.
    [6]
    羊衍秋,何玉晖,田杰,等. 阀切换技术在空气中SF6分析中的应用[J]. 色谱,2007,25(4):609-610.
    YANG Yanqiu, HE Yuhui, TIAN Jie, et al. Application of valve switch technique in fast analysis of SF6 in atmospheric samples[J]. Chinese Journal of Chromatography, 2007, 25(4): 609-610(in Chinese).
    [7]
    ALLWINE K J, LAMB B K, ESKRIDGE R. Wintertime dispersion in a mountainous basin at Roanoke, Virginia: Tracer study[J]. Journal of Applied Meteorology, 1992, 31: 1 296-1 311.
    [8]
    DIETZ R N. Gaseous-tracer technology and applications, BNL-33585[R]. US: Brookhaven National Laboratory, 1983.
    [9]
    王景书,余秀芬,张永义,等. 用示踪气体稀释法测量房间换气速度[J]. 环境科学,1990,11(4):65-69.
    [10]
    朱能. 示踪气体跟踪测量方法在空调通风上的应用[J]. 暖通空调,1999,29(2):58-62.
    ZHU Neng. Use of tracer gas measurement in HVAC systems[J]. Heating, Ventilating & Air Conditioning, 1999, 29(2): 58-62(in Chinese).
  • Cited by

    Periodical cited type(1)

    1. 李萍,王亚军,代记仁,田文春,薛克敏. 挤扭变形对低活化马氏体钢组织及蠕变性能的影响. 原子能科学技术. 2022(12): 2678-2688 . 本站查看

    Other cited types(0)

Catalog

    Article views (645) PDF downloads (1216) Cited by(1)

    /

    DownLoad:  Full-Size Img  PowerPoint
    Return
    Return