WGOTHIC Analysis on AP1000 Passive Containment Cooling Water

  • The WGOTHIC code was used to analyze the influence of the containment cooling water inventory to containment safety for different cases. The results show that if passive containment cooling system fails, the pressure in containment is beyond design limit after 1 000 s; if cooling water can’t be supplied after 72 h, the pressure in containment is beyond design limit after 0.9 d; if cooling water can’t be supplied after 19.6 d, the pressure in containment is beyond design limit but less than the breakdown pressure; if cooling water is supplied for 30 d, the air cooling can remove the decay heat without any aid. It is a reference for making emergency plan and improving containment design.