LI Lei, SUN Yu, WANG Jiao-ya, LIU Hong-tao. Research on Design Method of Main Control Room Intake Air Radioactive Monitoring[J]. Atomic Energy Science and Technology, 2014, 48(增刊2): 891-894. DOI: 10.7538/yzk.2014.48.S1.0891
Citation: LI Lei, SUN Yu, WANG Jiao-ya, LIU Hong-tao. Research on Design Method of Main Control Room Intake Air Radioactive Monitoring[J]. Atomic Energy Science and Technology, 2014, 48(增刊2): 891-894. DOI: 10.7538/yzk.2014.48.S1.0891

Research on Design Method of Main Control Room Intake Air Radioactive Monitoring

  • According to the design of the main control room intake gamma radiation dose rate monitoring channels in CPR1000 project and the study of relevant regulations and standards, a design method of main control room air inlet radioactive monitoring was presented. The measured object, equipment layout and chain operation were described. The threshold setting was explored using a calculation model established by MCNP software. The advantages, disadvantages and improvement ideas of this design were presented on the basis of calculation results.