CHEN Yong-wei, FU Jing-qiang, QIU He-wen, ZHANG Li-guo, YOU Dai-lun. Improvement and Optimization of Master/Bypass Valve Switching Process for Steam Generator Level Control of Nuclear Power Plant[J]. Atomic Energy Science and Technology, 2015, 49(3): 523-528. DOI: 10.7538/yzk.2015.49.03.0523
Citation: CHEN Yong-wei, FU Jing-qiang, QIU He-wen, ZHANG Li-guo, YOU Dai-lun. Improvement and Optimization of Master/Bypass Valve Switching Process for Steam Generator Level Control of Nuclear Power Plant[J]. Atomic Energy Science and Technology, 2015, 49(3): 523-528. DOI: 10.7538/yzk.2015.49.03.0523

Improvement and Optimization of Master/Bypass Valve Switching Process for Steam Generator Level Control of Nuclear Power Plant

  • According to the statistics of domestic nuclear power plant CPR1000 units, the common failure modes in the steam generator level control about the master/bypass valve switching process were described. The main modes include that the master/bypass valve switching threshold owes excellent, the master/bypass valve frequently switches and the master valve opens too late. And then a solution was raised about how to improve the master/bypass valve switching process, including switching point optimization, disturbance value control and difference control. This solution is performed in the project site and is verified feasible and effective.