ZHANG Ying-chao, JI Song-tao, WEI Yan-song, SHI Xiao-lei, XU Qian. Station Blackout Severe Accident Analysis of Spent Fuel Pool of 600 MWe NPP by Using MELCOR Code[J]. Atomic Energy Science and Technology, 2016, 50(3): 440-445. DOI: 10.7538/yzk.2016.50.03.0440
Citation: ZHANG Ying-chao, JI Song-tao, WEI Yan-song, SHI Xiao-lei, XU Qian. Station Blackout Severe Accident Analysis of Spent Fuel Pool of 600 MWe NPP by Using MELCOR Code[J]. Atomic Energy Science and Technology, 2016, 50(3): 440-445. DOI: 10.7538/yzk.2016.50.03.0440

Station Blackout Severe Accident Analysis of Spent Fuel Pool of 600 MWe NPP by Using MELCOR Code

  • Using MELCOR code, the spent fuel pool (SFP) of 600 MWe nuclear power plant (NPP) was modeled, and the station blackout severe accidents were calculated when the SFP was under normal condition, refuelling condition and the reactor accident condition. The calculation results show that fuel assemblies will melt down and hydrogen will generate, due to zirconium-water reaction, after the half height of fuel assemblies is uncovered. The influence of injection or spray on SFP accidents was analysed, and the results show that SFP accidents will be terminated and the water level of SFP will return up before fuel cladding damage if water is injected or sprayed into the SFP with the boiling evaporation mass rate.
  • loading

Catalog

    Turn off MathJax
    Article Contents

    /

    DownLoad:  Full-Size Img  PowerPoint
    Return
    Return