QM-400 CFD自然对流模型研究及验证

Research and Validation on CFD Natural Convection Model of QM-400

  • 摘要: 秦山第三核电厂乏燃料干式贮存模块QM-400是我国第一座投入商业运行的干式贮存设施,模块内的热量交换主要包括自然对流、热传导、耦合传热和辐射换热等。本文精确计算了典型环境温度下每个燃料篮的衰变热,运用商用计算流体动力学(CFD)软件FLUENT 14.0开展了网格敏感性分析,并建立了QM-400存储模块的自然对流CFD分析模型。结果表明,模块顶面、侧面以及贮存筒表面压力和温度分布符合自然对流规律,计算的测点温度与现场的实测温度符合良好,测点温度随环境温度的变化趋势也与实测趋势符合良好,证明了建立的CFD自然对流计算方法的正确性。本文结果为后续采用CFD方法进行取消绝热板后的温度场计算奠定了基础。

     

    Abstract: The spent fuel dry storage facility named QM-400 module for Third Qinshan Nuclear Power Co. Ltd. (TQNPC) is the first commercial dry storage facility in operation in China. The heat transfer in QM-400 mainly consists of natural convention, conduction, conjugate heat transfer and radiation, etc. The decay heat of each fuel basket was calculated accurately at typical surrounding temperature. Mesh sensitivity analysis was performed using commercial computational fluid dynamics (CFD) code FLUENT 14.0. A set of CFD simulation models on natural convection of QM-400 were developed. The results show that the distributions of the pressure and temperature on the cylinder surface meet the rules of natural convection. Good agreements are achieved between the simulated temperature and the measured temperature at the measured points and the simulated temperature trend varying with surrounding temperature agree well with the measured trend, which demonstrates the correctness of the calculation method of natural convection in this paper. This work can be the reference of the further CFD simulation on temperature distributions of dry storage facility without thermal insulation panels.

     

/

返回文章
返回